• FX5U-64MR-DS-Mitsubishi-PLC-controller.jpg
  • FX5U-64MR-DS-Mitsubishi-PLC-controller01.jpg
  • FX5U-64MR-DS-Mitsubishi-PLC-controller02.jpg
FX5U-64MR/DS Mitsubishi PLC controller
  • FX5U-64MR/DS
  • 220
  • 90
  • 2

FX5U-64MR/DS parameter description:DC power supply DC input, replaceable terminal block;Input 32 points DC24V source/sink, relay 32 points output;Built-in analog input 2 channels, built-in analog output 1 channel,Built-in high-speed counter up to 6 channels 200kHz + 2ch 10kHz,Built-in Ethernet port

Product details

FX5U-64MR/DS parameter description:

DC power supply DC input, replaceable terminal block;

Input 32 points DC24V source/sink, relay 32 points output;

Built-in analog input 2 channels, built-in analog output 1 channel,

Built-in high-speed counter up to 6 channels 200kHz + 2ch 10kHz,

Built-in Ethernet port 1 channel, built-in RS-485 port 1 channel


Mitsubishi FX5 series PLC relay output DC power supply FX5U-64MR/DS product specifications

1. Power supply specifications

[Rated voltage] DC24V

[Allowable voltage range] DC16.8V~28.8V

[Allowable instantaneous power failure time] 5ms or less

[Power supply fuse ratio] 250V 5A

[Inrush current] Maximum 65A 2ms or less/DC24V

[Power consumption] 40W

[DC24V power supply capacity] 740mA (530mA)

[DC5V built-in power supply capacity] 110mA (975mA)

2. Input specifications

[Input connection method] Detachable terminal block (M3 screw)

[Number of input points] 32 points

[Input method] Leakage/source

[Input signal voltage] DC24V +20%, -15%

[Input signal current] 5.3mA/DC24V, 4mA/DC24V after X020

[Input impedance] 4.3kΩ (X0~X17), 5.6kΩ or more after X020

[Input ON sensitivity current] 3.5mA or more (X0~X17), 3.0 or more after X020

[Input OFF sensitivity current] 1.5mA or less

[Input response frequency] X0~X5 200kHz, X6~X17 10kHz

[Input response time (H/W filter delay)] X0~X5 2.5μs or less; X6~X17 30μs or less when ON 50μs or less when OFF

[Input response time (digital filter setting value)] None, 10μs, 50μs, 0.1ms, 0.2, 0.4, 0.6, 1, 5, 10 (default value), 20, 70ms

[Input signal form] No-voltage contact input

For drain input: NPN open collector transistor

For source input: PNP open collector transistor

[Input circuit isolation] Optocoupler isolation

[Input action display] The LED on the panel lights up when the optocoupler is driven

3. Output specifications

[Output type] Relay

[Connection form] Detachable terminal block (M3 screw)

[Output points] 32 points

[External power supply] DC30V or less AC240V or less (AC250V or less when not corresponding to CE, UL, cUL specifications)

[Maximum load]

Resistive load: 2A/1 point, total load output per common terminal 1 point/common terminal 2A or less, output 4 points/common end 8A or less

Inductive load: 80VA

[Minimum load] DC5V 2mA

[Response time] About 10ms

[Circuit isolation] Mechanical isolation

[Output action display] The LED on the panel lights up when the relay coil is energized


4. Other specifications

[Dimensions H*W*D] 220*90*86mm

[Weight] 1.0kg


Please feel free to give your inquiry in the form below.We will reply you in 24 hours.